Best Boiler Banner.gif (38756 bytes)

 

Suggested Specifications

Furnish as shown on drawings, and build on location (  ) Model _________________ Best Boilers, 3-pass, full wetback, scotch-marine boiler.

Boiler(s) shall be design for ____________________ psi steam, ________________psi water. Heating surface shall be rated at 5 Sq.Ft. of heating surface per boiler horsepower. Boiler(s) shall contain a minimum of ____________ Sq.Ft. of fireside heating surface and have a heat release no greater than ________________ BTU per Cu. Ft./Hr. of furnace volume. Boiler(s) shall contain a minimum of ____________ gallons of water when filled to the normal water line. The Gross Stack Temperature shall not exceed 400°F.

The boiler design shall be of the welded steel horizontal firetube boiler type. Boiler(s) shall be completely fabricated and assembled on location or at shop by the manufacturer. Each boiler shall be design, built, inspected, tested and stamped in accordance with Section IV of the ASME Code and its addenda in effect.

The boiler manufacturer shall submit copies of (fireside) calculations in accordance with applicable ASME sections to the engineer.

The rear of each boiler shall be of full wet-back constriction, including two rear tube sheets, requiring no refractory in rear chamber area, back of boiler passes.

All firetubes shall be expanded, rolled and flared into tube sheets; welding of tubes into tube sheet will not be permitted.

Boiler tubes shall be 2 ½" diameter O.D. and shall be __________________ gauge.

a 20 inch access door with a poured refractory lining shall be provided in the rear reversing chamber.

Boiler insulating jacket shall be smooth finished heat resisting enamel on a steel jacket over 2 inch thick non-settling, moisture-proof fiber grass.

Boiler trim shall include, but shall not be limited to:

  1. Steam gauge.
  2. Safety valve as per ASME requirements.
  3. Water column with sight glass and tri-cocks.
  4. Water usage meter.

Phoenix Energy Telephone: 718-372-4210
2402 Neptune Avenue Fax: 718-372-0255
Brooklyn, New York 11224 General Information: info@bestboilers.com
www.bestboilers.com You are visitor:

Hit Counter

 
Send mail to info@Bestboilers.com with questions or comments about this web site.
Copyright © 1998
Phoenix Energy Management, Inc.
Last modified: March 24, 2009