Best Boiler Banner.gif (38756 bytes)

 

5-B Boiler Model

draw2.gif (19757 bytes)

Boiler Model/Size

5B-40

5B-50

5B-60

5B-70

5B-80

5B-90

5B-100

5B-125

Gross

Output

Horsepower

H.P.

40

50

60

70

80

90

100

125

Steam Radiation

SQ.FT.

5,600 7,000 8,400 9,800 11,200 12,600 14,000 17,500
Steam Thermal

MBH

1,338 1,674 2,009 2,343 2,678 3,013 3,348 4,184
Steam per hr. 212ºF

LB/HR

1,380 1,725 2,070 2,415 2,760 3,105 3,450 4,312
Net

Rating

Steam Radiation

SQ.FT.

4,211 5,376 6,499 7,580 8,663 9,747 10,831 13,535
Steam Thermal

MBH

1,039 1,300 1,560 1,819 2,079 2,339 2,600 3,248
Firing

Rate

Light Oil

GPH

12 15 18 21 24 27 30 37.5
Heavy Oil

GPH

11.3 14 16.8 19.5 22.3 25.1 27.9 34.9
Gas

MBH

1,675 2,093 2,510 2,930 3,350 3,787 4,185 5,232
Heating Surface (Fireside)

Furnace Volume

SQ.FT.

200 250 300 350 400 450 500 625

CU.FT.

32.51 37.54 42.52 47.55 53.00 58.04 63.49 76.60

Boiler Model/Size

5B-40

5B-50

5B-60

5B-70

5B-80

5B-90

5B-100

5B-125

A

Overall Length

FT.-IN.

7-6 1/2 8-6 3/8 9-6 1/4 10-6 1/4 11-7 1/4 12-7 1/4 13-8 1/4 16-5 1/2

B

Overall Width

IN.

64 64 64 64 64 64 64 64

C

Overall Height

IN.

72 72 72 72 72 72 72 72

D

Shell Length

FT.-IN.

5-0 1/2 6-0 3/8 7-0 1/4 8-0 1/4 9-1 1/4 10-1 1/4 11-2 1/4 13-9 1/2

E

Furnace Diameter

IN.

31 31 31 31 31 31 31 31

F

Furnace Length

IN.

53 1/2 65 3/8 77 1/4 89 1/4 102 1/4 114 1/4 127 1/4 158 1/2

G

Normal Water Line

IN.

63 5/8

63 5/8 63 5/8 63 5/8 63 5/8 63 5/8 63 5/8 63 5/8

H

Height-C.L. of Furnace

IN.

31 1/8

31 1/8 31 1/8 31 1/8 31 1/8 31 1/8 31 1/8 31 1/8

J

Depth-Reversing Chamber

IN.

8

8

8

8

8

8

8

8

K

Depth-Smoke Hood

IN.

21

21 21 21 21 21 21 21

L

Vent Outlet Dia.

IN.

12

12 14 14 14 16 16 18

M

Top-Front Rev. Chamber

IN.

61 7/16

61 7/16

61 7/16 61 7/16 61 7/16 61 7/16 61 7/16 61 7/16

P

Bottom-Front Rev. Chamber

IN.

30 5/8

30 5/8 30 5/8 30 5/8 30 5/8 30 5/8 30 5/8 30 5/8

Q

Top-Smoke Hood

IN.

70 1/4

70 1/4 70 1/4 70 1/4 70 1/4 70 1/4 70 1/4 70 1/4

R

Bottom-Smoke Hood

IN.

51 3/16

51 3/16 51 3/16 51 3/16 51 3/16 51 3/16 51 3/16 51 3/16

S

Saddle Width

IN.

7

7

7

7

7

7

7

7

T

Saddle Length

IN.

48

48 48 48 48 48 48 48

V

C.L. Front Saddle

IN.

12

12

12

12

12

12

12

12

W

C.L. Rear Saddle

IN.

35 47 59 71 84 96 109 140
  Steam Outlet Size

IN.

6

6

6

6

6

6

6

6

  Return Size

IN.

3

3

3

3

3

3

3

3

Boiler Model/Size

5B-40

5B-50

5B-60

5B-70

5B-80

5B-90

5B-100

5B-125

  Dry Weight (Approx.)

LBS.

3,820 4,530 5,886 6,165 7,075 7,785 8,285 9,644
  Operating Weight (Approx.)

LBS.

7,185 8,634 10,742 11,765 13,499 14,961 16,202 19,596


Information Request Form

Select the items that apply, and then let us know how to contact you.

Send product literature
Send company literature
Have a salesperson contact me

Name
Title
Company
Address
E-mail
Phone

 
Phoenix Energy Telephone: 718-372-4210
2402 Neptune Avenue Fax: 718-372-0255
Brooklyn, New York 11224 General Information: info@bestboilers.com
www.bestboilers.com You are visitor:

Hit Counter

 
Send mail to info@Bestboilers.com with questions or comments about this web site.
Copyright © 1998
Phoenix Energy Management, Inc.